Temperature profile data in the zone of flow establishment above a model air-cooled heat exchanger with 0.56 m2 face area operating under natural convection

Md Mizanur Rahman and Sivakumar Kumaresan and Chu, Chi Ming (2010) Temperature profile data in the zone of flow establishment above a model air-cooled heat exchanger with 0.56 m2 face area operating under natural convection. Journal of Applied Sciences, 10 (21). pp. 2673-2677. ISSN 1812-5654

[img]
Preview
Text
Temperature_profile_data_in_the_zone_of_flow_establishment_above_a_model_air.pdf

Download (48kB) | Preview

Abstract

The aim of this study was to analyze the temperature profile in the Zone of Flow Establishment (ZFE) above a 0.56 m2 hot screen placed at different height above an electrically heated model air-cooled heat exchanger operating under natural convection. Installation of screens increased the temperature difference from 30 to 140 K with respect to ambient that resulted in the air velocity increased at the inlet of the special duct from 0.67 m sec-1 to more than 2.0 m sec-1 under different heat loads ranging from 1 to 2.5 kW. The investigation of temperature profile was done above the hot screens placed at 0.35, 0.65, 0.95 and 1.25 m height over the electrically heated model air-cooled heat exchanger. The results show that the exit air temperature near to the electric heater and above the hot screens did not differ significantly but at heights of 0.09 m and upward the temperature difference differed by 2 to 6 K depending on the height of the hot screens. Maximum temperature difference was observed for hot screen placed at 0.65 and 0.95 m. Although, the temperatures at the beginning of the zone of flow establishment were almost the same for eveiy heat load, the radial profile of temperature turned from parabolic in shape to uniformly flat for the configuration without screen and with screen respectively. This indicates turbulence increase above the hot screens. © Asian Network for Scientific Information.

Item Type: Article
Keyword: Cooling tower, Heat exchanger, Natural convection, Natural draft, Plume
Subjects: Q Science > QC Physics
Department: SCHOOL > School of Engineering and Information Technology
Depositing User: ADMIN ADMIN
Date Deposited: 08 Mar 2011 19:01
Last Modified: 13 Oct 2017 09:42
URI: https://eprints.ums.edu.my/id/eprint/2114