Installation of high resistance grounding system on the ungrounded system at offshore platform

Alvin Teo Tuan Lee and Mazlina Mamat and Pungut Ibrahim and Nader Nassif Barsoum and Hoe Tung Yew (2021) Installation of high resistance grounding system on the ungrounded system at offshore platform.

[img] Text
Installation of high resistance grounding system on the ungrounded system at offshore platform.ABSTRACT.pdf

Download (59kB)
[img] Text
Installation of high resistance grounding system on the ungrounded system at offshore platform.pdf
Restricted to Registered users only

Download (1MB) | Request a copy

Abstract

Single line to earth fault usually can be seen in the ungrounded system. The ungrounded system is used widely in offshore platforms due to its advantages over the overvoltage whenever a fault occurs in the power systems. Continuous production with less interruption is vital in the oil and gas industry to achieve the production rate target. The grounding system has evolved for the past years and improvements have been made to the ungrounded system that has been around the years in the industry. The ungrounded system has been the best grounding system when the power system needs to maintain its operation with the presence of tolerable fault such as the single line to earth fault. Some facilities have included the feature of tripping the main circuit breaker whenever there is ground fault on the non-critical equipment. This has been unproductive to the operation and time consuming in restarting the plant facility after power failure or shutdown. Kikeh offshore platform is having the same situation whenever the ground fault occurs the main circuit breaker tripped and affects the operation badly. The High Resistance Grounding (HRG) design has proved to be able to sustain the fault and at the same time allows the plant to continue operating without any unnecessary shutdown. This improves the downtime and increases productivity. Furthermore, arc hazards to personnel and the classification flammable gas area can be minimized.

Item Type: Proceedings
Keyword: High resistance grounding , hrg , Earth fault , Ungrounded , Arc
Subjects: Q Science > QA Mathematics > QA1-939 Mathematics > QA71-90 Instruments and machines > QA75.5-76.95 Electronic computers. Computer science > QA76.75-76.765 Computer software
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1-9971 Electrical engineering. Electronics. Nuclear engineering
Department: FACULTY > Faculty of Engineering
Depositing User: DG MASNIAH AHMAD -
Date Deposited: 22 Apr 2022 15:07
Last Modified: 22 Apr 2022 15:07
URI: https://eprints.ums.edu.my/id/eprint/32374

Actions (login required)

View Item View Item