Chu, Chi Ming (2002) A preliminary method for estimating the effective plume chimney height above a forced-draft air-cooled heat exchanger operating under natural convection. Heat Transfer Engineering, 23 (3). pp. 3-12. ISSN 0145-7632
Full text not available from this repository.Abstract
A preliminary method to estimate the plume chimney height for a still ambient condition is presented here. The method predicts a negligible plume chimney effect on the laboratory-size test exchanger Measurements from an industrial-size heat exchanger (2.4 x 60 m(2)) in forced-draft mode have been compared with simulations incorporating the new method. The simulated heat toads agree with the 11 measurements to within +25/-40%, compared to an average of +70% if calculated by an existing formula and -75% by assuming negligible effective plume chimney height. Agreement between the new method and the measured exchanger performance did not appear to be affected by wind speeds in the range 2-6 m/s.
Item Type: | Article |
---|---|
Keyword: | Thermodynamics, Engineering, Mechanical, Mechanics, Chimney height |
Subjects: | T Technology > TH Building construction > TH1-9745 Building construction > TH7005-7699 Heating and ventilation. Air conditioning |
Department: | SCHOOL > School of Engineering and Information Technology |
Depositing User: | ADMIN ADMIN |
Date Deposited: | 05 Jan 2012 16:25 |
Last Modified: | 17 Feb 2015 15:24 |